Lennox Furnace Error Code E016 usually means the furnace control has detected a low-pressure switch circuit problem, most often caused by a blocked condensate drain, restricted intake or exhaust vent, or a stuck pressure switch. The single most likely fix is to clear the condensate tubing and venting, then reset power and confirm the pressure switch closes properly during inducer operation.
On many Lennox furnace platforms, Lennox Furnace Error Code E016 points to a draft-proving issue in the pressure switch circuit. The pressure switch is a safety device that verifies the inducer motor is creating the correct negative pressure before the hot surface ignitor, gas valve, and burners are allowed to operate. If the switch stays open when it should close, opens during a heating cycle, or sends an unstable signal to the control board, the furnace locks out and posts E016.
This does not automatically mean the pressure switch itself is defective. In the field, the actual cause is often external to the switch: a clogged condensate trap, water in the pressure tubing, a partially blocked flue, a plugged intake, or an inducer wheel that is not pulling enough draft. Loose wiring, corroded terminals, and a damaged wiring harness between the pressure switch and PCB can also create the same fault signature.
Because the pressure switch is part of the combustion safety circuit, E016 should be treated seriously. Bypassing the switch, jumping wires, or forcing the furnace to run is unsafe and can allow improper venting, flame rollout risk, or carbon monoxide hazards. The goal is to find out why the switch is not proving draft, not to defeat the safety circuit.
High-efficiency Lennox furnaces produce condensate that must drain freely through the trap and tubing. If the trap fills with sludge or the hose kinks, water backs up into the inducer housing or pressure tubing and the switch cannot read pressure correctly. This is one of the most common causes of E016.
Leaves, nests, snow, ice, and even sagging vent sections can reduce airflow through the combustion system. When the inducer cannot establish proper draft, the pressure switch stays open or drops out during operation. A vent restriction may be intermittent, especially during wind, freezing conditions, or heavy rain.
The switch diaphragm can weaken with age, and the port can plug with condensate residue. The rubber or vinyl tubing may split, collapse, or fill with water, causing a false pressure reading. A pressure switch problem should be confirmed with testing, not guessed.
A weak inducer motor, damaged capacitor on applicable designs, or debris on the inducer wheel can reduce draft enough to trigger the error. Sometimes the motor runs but does not reach the required speed under load. Bearing wear and water intrusion are also common failure points.
If the wiring harness between the pressure switch and control board has loose spade connectors, corrosion, or broken conductors, the board may read the switch state incorrectly. In rarer cases, the furnace PCB input circuit fails and reports a pressure switch fault even when the switch and draft are normal. Electrical diagnosis is needed before replacing a board.
Follow the steps below one at a time — many error codes can be fixed faster than they look.
Tools you may need: screwdriver, multimeter, flashlight
Safety warning: Disconnect power before opening any panels or touching internal components.
Yes, you can try a basic reset by shutting off furnace power for 15 to 30 minutes and then restoring power. If Lennox Furnace Error Code E016 was caused by a temporary lockout, it may clear. If the code comes back, the furnace still detects a pressure switch or draft problem that needs inspection.
No. E016 involves the combustion safety circuit, so the furnace should not be forced to run. The pressure switch is there to confirm proper venting and inducer draft before ignition. If that circuit is bypassed or ignored, the unit may vent improperly and create a serious safety hazard.
The most common repair is clearing a blocked condensate trap or drain line and removing any intake or exhaust vent obstruction. Those two issues often prevent the pressure switch from proving draft even though the switch itself is still good. A cracked pressure tube is another common and inexpensive fix.
Cost depends on the cause. A simple condensate cleaning, tubing repair, or vent clearing is usually on the low end. Replacing a pressure switch is moderate, while an inducer motor assembly or PCB diagnosis and replacement costs more. The final price depends on labor, access, and whether multiple faults are present.
Usually not directly. A dirty air filter more often causes overheating or limit switch faults because it restricts supply airflow, not combustion draft. However, multiple airflow and drainage problems can occur at the same time, so it is still smart to replace a heavily clogged filter while troubleshooting the furnace.
Call a professional if you have cleared the drain and venting, inspected the tubing and wiring, and E016 still returns. You should also call immediately if the inducer sounds abnormal, water keeps backing up, you suspect a cracked vent, or you are not comfortable testing live electrical circuits with a multimeter.
Try these recommended tools — used by thousands to solve the same issue:
As an Amazon Associate / affiliate partner we may earn from qualifying purchases.
Browse More Fixes